Single Core Cables

Applications

6491X Cable H07V-R/H07V-U is suitable for power and lighting circuits and building wiring. The cable is intended for use in semi-flush exposed conduits and embedded conduits as well as in closed installation ducts, and is ideal for the internal wiring of appliances.

Characteristics

Voltage Rating (Uo/U)
450/750V

Temperature Rating
-15°C to +70°C

Minimum Bending Radius

  • Up to 10mm²: 3 × overall diameter
  • 10mm² to 25mm²: 4 × overall diameter
  • Above 25mm²: 5 × overall diameter

Construction

Conductor
Class 2 stranded copper conductor

Insulation
PVC (Polyvinyl Chloride)

Insulation Colour
Red
Black
Note
Blue
Yellow
White
Green
Brown
Grey
Note: 5mm² to 10mm² also available as H07V-U Class 1 solid copper conductor

Dimensions

Nominal cross sectional area (Mm²) Minimum number of wires in conductor (Cu) Nominal thickness of insulation (mm) Nominal overall diameter (mm) Maximum resistance of conductor at 20°c (ohms/km) annealed cu conductor Nominal weight (kg/km)
1.5 7 0.7 2.9 12.1 22
2.5 7 0.8 3.6 7.41 32
4 7 0.8 4.1 4.61 50
6 7 0.8 4.7 3.08 71
10 7 1.0 5.9 1.83 110
16 7 1.0 6.8 1.15 164
25 7 1.2 8.4 0.727 256
35 7 1.2 9.4 0.524 346
50 19 1.4 11.0 0.387 473
70 19 1.4 12.7 0.268 674
95 19 1.6 14.7 0.193 913
120 37 1.6 16.2 0.153 1150
150 37 1.8 18.0 0.124 1416
185 37 2.0 20.0 0.0991 1749
240 37 2.2 23.0 0.0754 2317
300 61 2.4 25.2 0.0601 3049

Frequentyl Asked Question

Eurogrid Electricals is a manufacturer, positioned as a trusted MCB Changeover Manufacturer in India rather than a reseller. 

Eurogrid's MCB changeover switches are built to IEC 60947-3, the international standard for low-voltage switchgear and switching devices. 

Check for compliance with relevant IEC standards, a documented product range across amperage ratings, and manufacturing (not just trading) credentials. 

Key features to look for include compact design, double-break contacts for safer isolation, DIN rail mounting for easy panel integration, and energy-efficient operation. 

 It transfers electrical load from the main power source to a backup source (like a generator) during an outage, ensuring uninterrupted power supply.

A manual changeover requires someone to physically switch the source, while an automatic transfer switch (ATS) detects a power failure and switches sources without human intervention.

It depends on the electrical system: 2-pole (2P) suits single-phase setups, while 4-pole (4P) is used for three-phase systems where neutral switching is also required. 

Yes — MCB changeover switches are specifically designed to transfer load between mains and a backup source like a generator during outages.

It's based on the connected load's current draw and the cable's current-carrying capacity — the MCB rating should protect the cable, not just the appliance, typically matched via a load calculation rather than guesswork.